Data hall / white space.

The room everyone thinks is the safe one. It is full of energized equipment, worked mostly by people who are not qualified persons, at temperatures that would trigger a heat program anywhere else.

The assumption that fails

"It's only rack power." A dual-corded rack at 415/240 V with a 60 A whip is energized electrical equipment. Removing a receptacle cover, working on a whip termination or troubleshooting a rack PDU is electrical work — and the person doing it is frequently an IT technician, not a qualified person.

§ Electrical

Common finding

Rack PDU work performed by IT staff with no electrical training, in a facility whose electrical safety program never contemplated them. The program covers the electricians; the people actually touching energized equipment most often are not in it.

§ Heat — the overlooked one

What this means in a data center

Contained hot aisles routinely run 95–110 °F. There is no OSHA heat standard in force as a specific standard, but heat illness is cited under the General Duty Clause and OSHA has an active enforcement emphasis.

The compounding factor nobody addresses: a technician in arc-rated clothing in a contained hot aisle is carrying a heat load that generic heat guidance does not model and generic arc flash guidance ignores. Layered AR clothing has a real thermal burden, and the work is in the hottest part of the building.

Practical controls: work rotation, cold-aisle staging, scheduled breaks, hydration, and — where the task allows — doing the work from the cold aisle.

§ Physical

Train the people who are actually in the hall

Awareness training for unqualified staff

A short session on boundaries, labels, what not to touch and what to do if something goes wrong. Cheap, fast, and closes a real gap.