■ Tool NFPA 70E · 2027 edition

PPE category — and when the table cannot help you.

Two methods exist. You pick one per task and you do not mix them. This tool works the table method and, just as importantly, tells you when the table method does not apply to what you are looking at.

§ Which method are you using?

Incident energy analysis methodArc flash PPE category method
InputAn engineering study — cal/cm² at a working distanceEquipment type, voltage, available fault current, clearing time
OutputA number. Select PPE from Table 130.5(G)A category, 1 through 4. Select PPE from Table 130.7(C)(15)(c)
Use it whenYou have a study, and the label carries an incident energy valueYou have no study and your equipment falls inside the table parameters
Do notUse the study number to pick a category, then dress to the categoryUse the table when your fault current or clearing time exceeds the stated parameters

§ Table method walker

This is not an engineering study. This tool shows method, not a verdict for your equipment. Incident energy, boundaries and PPE for your specific installation come from your own arc flash study, your employer's electrical safety program and the published standard. Verify everything against NFPA 70E 2027.

§ What the categories mean

CategoryMinimum arc ratingPractical meaning
14 cal/cm²AR shirt and pants, face shield, hard hat, safety glasses, hearing protection, leather gloves
28 cal/cm²Adds a balaclava or hood — the face and neck coverage is the difference
325 cal/cm²Arc flash suit and hood. This is a two-person job in practice, and now formally so under 130.2(A)(2) if a permit is required
440 cal/cm²Full suit and hood. Above 40 cal/cm², the standard's guidance is that no PPE is a substitute for de-energizing

§ If you have a study — Table 130.5(G)

Where the label carries an incident energy value, you do not use categories at all. Table 130.5(G) has two bands:

Incident energy at the working distanceRequired PPE
1.2 – 12 cal/cm²AR clothing with an arc rating ≥ the estimated incident energy; AR long-sleeve shirt and pants, coverall or arc flash suit (SR); AR face shield + balaclava, or arc flash suit hood (SR); AR outerwear as needed; heavy-duty leather, AR or rubber insulating gloves with protectors (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear
Greater than 12 cal/cm²AR clothing with an arc rating ≥ the estimated incident energy; AR shirt and pants, coverall or arc flash suit (SR); arc flash suit hood — no face-shield option; AR outerwear as needed; AR gloves or rubber insulating gloves with protectors (SR) — leather-only gloves are no longer permitted; hard hat; safety glasses or goggles (SR); hearing protection; leather footwear

SR = selection of one in the group is required. AN = as needed. The practical difference between the bands is the hood and the gloves: above 12 cal/cm² a face shield and balaclava will not do, and plain leather gloves will not do.

§ When the table method fails

Never mix methods

Reading a cal/cm² value off a label and then dressing to the "matching" category is a method error. The two methods use different assumptions. Use the number with Table 130.5(G), or use the equipment class with the category tables. Not both.

The tables are the easy part

Judgment on the hard cases

The 16-hour class covers incident energy methods, the table limits, and how to challenge a label you no longer trust.