Four hazards. Run your string through all of them.
Article 360 requires the battery risk assessment to address four separate hazard categories, each with its own PPE determination. This checks the three quantitative ones against your string.
§ Threshold check
§ The four categories
Full detail, including the chemistry comparison and the flow-battery note, is on the Article 360 page. The short version:
Chemical — electrolyte burns. Assess against equipment design, the SDS, and the condition of maintenance.
Contact thermal — burns from current heating through a dropped tool, a ring or a watch band. Threshold 1,000 W. Independent of voltage.
Electric shock — 100 V and 40 mA DC, 50 V and 5 mA AC.
Arc flash — 150 V DC and 1.2 cal/cm², with the 1 mm-per-volt separation guidance for likelihood.
§ While you are in the room
Article 360 requires battery room and enclosure signs to carry electrical hazards (shock, arc flash and thermal), chemical hazards, and a PPE and access notice. Where multiple chemistries share a room, the chemical warning must reflect the worst case present. Most existing signs predate the thermal requirement.
Battery rooms in the 16-hour class
Article 360, the four categories, the thresholds and the NFPA 855 boundary — against real UPS and BESS configurations.