SafePath tables.
The reference set, on one page, in the order you actually reach for them. Summarised for field use — the published standard is the source of truth.
Tables are cited under the 2027 numbering — Table 130.4(E)(a) for AC shock boundaries, 130.4(E)(b) for DC. Older material may use a different subdivision letter; that is prior-edition numbering. Values here are 2027.
§ Table 130.4(E)(a) — Shock approach boundaries, AC
| Nominal system voltage, phase to phase | Limited approach | Restricted — exposed movable conductor | Restricted — exposed fixed circuit part |
|---|---|---|---|
| Less than 50 V | Not specified | Not specified | Not specified |
| 50 V – 150 V | 10 ft 0 in (3.1 m) | 3 ft 6 in (1.0 m) | Avoid contact |
| 151 V – 750 V | 10 ft 0 in (3.1 m) | 3 ft 6 in (1.0 m) | 1 ft 0 in (0.31 m) |
| 751 V – 5 kV | 10 ft 0 in (3.1 m) | 3 ft 6 in (1.0 m) | 2 ft 1 in (0.63 m) |
| 5.1 kV – 15 kV | 10 ft 0 in (3.1 m) | 5 ft 0 in (1.5 m) | 2 ft 2 in (0.65 m) |
| 15.1 kV – 36 kV | 10 ft 0 in (3.1 m) | 6 ft 0 in (1.8 m) | 2 ft 7 in (0.77 m) |
| 36.1 kV – 46 kV | 10 ft 0 in (3.1 m) | 8 ft 0 in (2.5 m) | 2 ft 10 in (0.84 m) |
| 46.1 kV – 72.5 kV | 10 ft 0 in (3.1 m) | 8 ft 0 in (2.5 m) | 3 ft 4 in (1.0 m) |
| 72.6 kV – 121 kV | 10 ft 8 in (3.3 m) | 8 ft 0 in (2.5 m) | 3 ft 9 in (1.2 m) |
| 121.1 kV – 145 kV | 11 ft 0 in (3.4 m) | 10 ft 0 in (3.1 m) | 4 ft 4 in (1.3 m) |
| 145.1 kV – 169 kV | 11 ft 8 in (3.6 m) | 11 ft 8 in (3.6 m) | 4 ft 10 in (1.5 m) |
| 169.1 kV – 242 kV | 13 ft 0 in (4.0 m) | 13 ft 0 in (4.0 m) | 6 ft 8 in (2.1 m) |
| 242.1 kV – 362 kV | 15 ft 4 in (4.7 m) | 15 ft 4 in (4.7 m) | 11 ft 2 in (3.5 m) |
| 362.1 kV – 420 kV | 19 ft 0 in (5.8 m) | 19 ft 0 in (5.8 m) | 14 ft 0 in (4.3 m) |
| 420.1 kV – 550 kV | 19 ft 0 in (5.8 m) | 19 ft 0 in (5.8 m) | 16 ft 8 in (5.1 m) |
| 550.1 kV – 800 kV | 23 ft 9 in (7.2 m) | 23 ft 9 in (7.2 m) | 22 ft 7 in (6.9 m) |
- For single-phase systems above 250 V, select the range equal to the maximum phase-to-ground voltage × 1.732.
- "Exposed movable conductor" means a conductor whose position is not under the worker's control — typically overhead line conductors on poles.
- Restricted approach distances assume an elevation ≤ 900 m (3,000 ft); adjust above that.
- See 130.5(E) for the arc flash boundary — it is not in this table.
§ Table 130.4(E)(b) — Shock approach boundaries, DC
| Nominal potential difference | Limited approach | Restricted — movable | Restricted — fixed |
|---|---|---|---|
| Less than 50 V | Not specified | Not specified | Not specified |
| 50 V – 300 V | 10 ft 0 in (3.1 m) | 3 ft 6 in (1.0 m) | Avoid contact |
| 301 V – 1 kV | 10 ft 0 in (3.1 m) | 3 ft 6 in (1.0 m) | 1 ft 0 in (0.3 m) |
| 1.1 kV – 5 kV | 10 ft 0 in (3.1 m) | 5 ft 0 in (1.5 m) | 1 ft 5 in (0.5 m) |
| 5.1 kV – 15 kV | 10 ft 0 in (3.1 m) | 5 ft 0 in (1.5 m) | 2 ft 2 in (0.7 m) |
| 15.1 kV – 45 kV | 10 ft 0 in (3.1 m) | 8 ft 0 in (2.5 m) | 2 ft 9 in (0.8 m) |
| 45.1 kV – 75 kV | 10 ft 0 in (3.1 m) | 8 ft 0 in (2.5 m) | 3 ft 6 in (1.0 m) |
| 75.1 kV – 150 kV | 10 ft 8 in (3.3 m) | 10 ft 0 in (3.1 m) | 3 ft 10 in (1.2 m) |
| 150.1 kV – 250 kV | 11 ft 8 in (3.6 m) | 11 ft 8 in (3.6 m) | 5 ft 3 in (1.6 m) |
| 250.1 kV – 500 kV | 20 ft 0 in (6.0 m) | 20 ft 0 in (6.0 m) | 11 ft 6 in (3.5 m) |
| 500.1 kV – 800 kV | 26 ft 0 in (8.0 m) | 26 ft 0 in (8.0 m) | 16 ft 5 in (5.0 m) |
§ Table 130.5(C)(3) — Likelihood of an arc flash incident
| Task | Condition | Likelihood |
|---|---|---|
| Reading a panel meter while operating a meter switch | Any | No |
| Infrared thermography and non-contact inspection outside the restricted approach boundary, no door or cover opened | — | No |
| Work on control circuits ≤ 125 V ac/dc, no other exposed equipment above 125 V, including opening hinged covers | — | No |
| Examination of insulated cable with no manipulation | — | No |
| DC: maintenance on a single battery cell or multi-cell units in an open rack | — | No |
| Battery equipment below 600 V where conductor separation exceeds 1 mm per volt | — | No |
| Operation of a breaker, switch, contactor or starter | Normal | No |
| Arc-resistant equipment, doors closed and secured, within rated fault current and clearing time, for racking and insertion tasks | — | No |
| Operation of a breaker, switch, contactor or starter | Abnormal | Yes |
| Operation of a breaker or switch the first time after installation or maintenance | — | Yes |
| AC: work on energized conductors or circuit parts, including electrical testing | Any | Yes |
| DC: work on energized series-connected battery cell conductors, including testing | — | Yes |
| Removal or installation of breakers or switches | — | Yes |
| Opening hinged doors, covers or bolted covers exposing bare energized parts, including DC battery terminal covers | — | Yes |
| Application of temporary protective grounding, after the voltage test | — | Yes |
| Work on exposed control circuits above 120 V | — | Yes |
| Insertion or removal of MCC starter buckets | — | Yes |
| Insertion or removal (racking) of breakers or starters from cubicles, doors open or closed | — | Yes |
| Insertion or removal of plug-in devices into or from busways | — | Yes |
Excerpt of the key rows. "Normal operating condition" per ' + m('110.2(B)') + ' Exception No. 1. Read the full table in the published standard.
§ Table 130.7(C)(15)(a) — Arc flash PPE categories, AC
| Equipment | Category | Arc flash boundary |
|---|---|---|
| Panelboards or other equipment ≤ 240 V | 1 | 19 in (485 mm) |
| Panelboards or other equipment > 240 V and ≤ 600 V | 2 | 3 ft (900 mm) |
| 600 V class MCC — fault ≤ 65 kA, clearing ≤ 0.03 s | 2 | 5 ft (1.5 m) |
| 600 V class MCC — fault ≤ 42 kA, clearing ≤ 0.33 s | 4 | 14 ft (4.3 m) |
| 600 V class switchgear and switchboards | 4 | 20 ft (6 m) |
| Other 600 V class equipment | 2 | 5 ft (1.5 m) |
| NEMA E2 motor starters, 2.3 – 7.2 kV | 4 | 40 ft (12 m) |
| Metal-clad switchgear, 1 – 15 kV | 4 | 40 ft (12 m) |
| Metal-enclosed interrupter switchgear, 1 – 15 kV | 4 | 40 ft (12 m) |
| Other equipment 1 – 15 kV | 4 | 40 ft (12 m) |
| Arc-resistant equipment, doors closed and secured, within rating | N/A | N/A |
The two MCC rows are the same equipment at two categories. The only difference is clearing time — and clearing time depends on maintenance.
For equipment ≤ 600 V protected by upstream current-limiting fuses or breakers rated 200 A or less, the category may be reduced by one — but never below Category 1.
§ Table 130.7(C)(15)(b) — Arc flash PPE categories, DC
Storage batteries, DC switchboards and other DC supply sources — excluding Article 320 capacitors — greater than 150 V and up to 600 V, based on a 2-second arc duration at a 455 mm (18 in) working distance.
| Available fault current | Category | Arc flash boundary |
|---|---|---|
| Less than 1.5 kA | 2 | 3 ft (900 mm) |
| 1.5 kA to less than 3 kA | 2 | 4 ft (1.2 m) |
| 3 kA to less than 7 kA | 3 | 6 ft (1.8 m) |
| 7 kA to less than 10 kA | 4 | 8 ft (2.5 m) |
§ Table 130.7(C)(15)(c) — PPE by category
| Category | Minimum arc rating | Key clothing and equipment |
|---|---|---|
| 1 | 4 cal/cm² (16.75 J/cm²) | AR shirt and pants or coverall; face shield or hood; hard hat; safety glasses or goggles (SR); hearing protection (ear canal inserts); leather, AR or rubber insulating gloves (SR); leather footwear (AN) |
| 2 | 8 cal/cm² (33.5 J/cm²) | AR shirt and pants or coverall; hood, or face shield plus balaclava; hard hat; safety glasses or goggles (SR); hearing protection; gloves (SR); leather footwear |
| 3 | 25 cal/cm² (104.7 J/cm²) | Full AR layered system — shirt, pants, coverall, suit jacket and pants as required; arc flash suit hood; gloves (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear |
| 4 | 40 cal/cm² (167.5 J/cm²) | Full AR layered system; arc flash suit hood; gloves (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear |
AN = as needed. AR = as required. SR = selection of one in the group required.
§ Table 130.5(G) — Incident energy analysis method
| Incident energy at the working distance | Required PPE |
|---|---|
| 1.2 – 12 cal/cm² | AR clothing with an arc rating ≥ the estimated incident energy; AR long-sleeve shirt and pants, coverall or arc flash suit (SR); AR face shield plus balaclava, or arc flash suit hood (SR); AR outerwear as needed; heavy-duty leather, AR or rubber insulating gloves with protectors (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear |
| Greater than 12 cal/cm² | AR clothing with an arc rating ≥ the estimated incident energy; AR shirt and pants, coverall or arc flash suit (SR); arc flash suit hood — no face-shield option; AR outerwear as needed; AR gloves or rubber insulating gloves with protectors (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear |
Above 12 cal/cm² a face shield and balaclava will not do — you need the hood. And plain heavy-duty leather gloves will not do — you need arc-rated gloves or rubber insulating gloves with protectors.
§ Tables 130.7(C)(7)(a) and (b) — Rubber insulating equipment
| Class | Max AC use voltage (rms) | Max DC use voltage (avg) | Min. protector / glove cuff distance |
|---|---|---|---|
| 00 | 500 V | 750 V | 13 mm (0.5 in) |
| 0 | 1,000 V | 1,500 V | 13 mm (0.5 in) |
| 1 | 7,500 V | 11,250 V | 25 mm (1 in) |
| 2 | 17,000 V | 25,500 V | 51 mm (2 in) |
| 3 | 26,500 V | 39,750 V | 76 mm (3 in) |
| 4 | 36,000 V | 54,000 V | 102 mm (4 in) |
| Equipment | When to test |
|---|---|
| Gloves | Before first issue; every 6 months thereafter |
| Sleeves | Before first issue; every 12 months thereafter |
| Blankets | Before first issue; every 12 months thereafter |
| Covers | If insulating value is suspect |
| Line hose | If insulating value is suspect |
New insulating equipment must have been tested within the previous 12 months before being placed in service. Issued equipment is retested per this table.