SafePath tables.

The reference set, on one page, in the order you actually reach for them. Summarised for field use — the published standard is the source of truth.

Everything on this page is the 2027 edition

Tables are cited under the 2027 numbering — Table 130.4(E)(a) for AC shock boundaries, 130.4(E)(b) for DC. Older material may use a different subdivision letter; that is prior-edition numbering. Values here are 2027.

§ Table 130.4(E)(a) — Shock approach boundaries, AC

Nominal system voltage, phase to phaseLimited approachRestricted — exposed movable conductorRestricted — exposed fixed circuit part
Less than 50 VNot specifiedNot specifiedNot specified
50 V – 150 V10 ft 0 in (3.1 m)3 ft 6 in (1.0 m)Avoid contact
151 V – 750 V10 ft 0 in (3.1 m)3 ft 6 in (1.0 m)1 ft 0 in (0.31 m)
751 V – 5 kV10 ft 0 in (3.1 m)3 ft 6 in (1.0 m)2 ft 1 in (0.63 m)
5.1 kV – 15 kV10 ft 0 in (3.1 m)5 ft 0 in (1.5 m)2 ft 2 in (0.65 m)
15.1 kV – 36 kV10 ft 0 in (3.1 m)6 ft 0 in (1.8 m)2 ft 7 in (0.77 m)
36.1 kV – 46 kV10 ft 0 in (3.1 m)8 ft 0 in (2.5 m)2 ft 10 in (0.84 m)
46.1 kV – 72.5 kV10 ft 0 in (3.1 m)8 ft 0 in (2.5 m)3 ft 4 in (1.0 m)
72.6 kV – 121 kV10 ft 8 in (3.3 m)8 ft 0 in (2.5 m)3 ft 9 in (1.2 m)
121.1 kV – 145 kV11 ft 0 in (3.4 m)10 ft 0 in (3.1 m)4 ft 4 in (1.3 m)
145.1 kV – 169 kV11 ft 8 in (3.6 m)11 ft 8 in (3.6 m)4 ft 10 in (1.5 m)
169.1 kV – 242 kV13 ft 0 in (4.0 m)13 ft 0 in (4.0 m)6 ft 8 in (2.1 m)
242.1 kV – 362 kV15 ft 4 in (4.7 m)15 ft 4 in (4.7 m)11 ft 2 in (3.5 m)
362.1 kV – 420 kV19 ft 0 in (5.8 m)19 ft 0 in (5.8 m)14 ft 0 in (4.3 m)
420.1 kV – 550 kV19 ft 0 in (5.8 m)19 ft 0 in (5.8 m)16 ft 8 in (5.1 m)
550.1 kV – 800 kV23 ft 9 in (7.2 m)23 ft 9 in (7.2 m)22 ft 7 in (6.9 m)

§ Table 130.4(E)(b) — Shock approach boundaries, DC

Nominal potential differenceLimited approachRestricted — movableRestricted — fixed
Less than 50 VNot specifiedNot specifiedNot specified
50 V – 300 V10 ft 0 in (3.1 m)3 ft 6 in (1.0 m)Avoid contact
301 V – 1 kV10 ft 0 in (3.1 m)3 ft 6 in (1.0 m)1 ft 0 in (0.3 m)
1.1 kV – 5 kV10 ft 0 in (3.1 m)5 ft 0 in (1.5 m)1 ft 5 in (0.5 m)
5.1 kV – 15 kV10 ft 0 in (3.1 m)5 ft 0 in (1.5 m)2 ft 2 in (0.7 m)
15.1 kV – 45 kV10 ft 0 in (3.1 m)8 ft 0 in (2.5 m)2 ft 9 in (0.8 m)
45.1 kV – 75 kV10 ft 0 in (3.1 m)8 ft 0 in (2.5 m)3 ft 6 in (1.0 m)
75.1 kV – 150 kV10 ft 8 in (3.3 m)10 ft 0 in (3.1 m)3 ft 10 in (1.2 m)
150.1 kV – 250 kV11 ft 8 in (3.6 m)11 ft 8 in (3.6 m)5 ft 3 in (1.6 m)
250.1 kV – 500 kV20 ft 0 in (6.0 m)20 ft 0 in (6.0 m)11 ft 6 in (3.5 m)
500.1 kV – 800 kV26 ft 0 in (8.0 m)26 ft 0 in (8.0 m)16 ft 5 in (5.0 m)

§ Table 130.5(C)(3) — Likelihood of an arc flash incident

TaskConditionLikelihood
Reading a panel meter while operating a meter switchAnyNo
Infrared thermography and non-contact inspection outside the restricted approach boundary, no door or cover openedNo
Work on control circuits ≤ 125 V ac/dc, no other exposed equipment above 125 V, including opening hinged coversNo
Examination of insulated cable with no manipulationNo
DC: maintenance on a single battery cell or multi-cell units in an open rackNo
Battery equipment below 600 V where conductor separation exceeds 1 mm per voltNo
Operation of a breaker, switch, contactor or starterNormalNo
Arc-resistant equipment, doors closed and secured, within rated fault current and clearing time, for racking and insertion tasksNo
Operation of a breaker, switch, contactor or starterAbnormalYes
Operation of a breaker or switch the first time after installation or maintenanceYes
AC: work on energized conductors or circuit parts, including electrical testingAnyYes
DC: work on energized series-connected battery cell conductors, including testingYes
Removal or installation of breakers or switchesYes
Opening hinged doors, covers or bolted covers exposing bare energized parts, including DC battery terminal coversYes
Application of temporary protective grounding, after the voltage testYes
Work on exposed control circuits above 120 VYes
Insertion or removal of MCC starter bucketsYes
Insertion or removal (racking) of breakers or starters from cubicles, doors open or closedYes
Insertion or removal of plug-in devices into or from buswaysYes

Excerpt of the key rows. "Normal operating condition" per ' + m('110.2(B)') + ' Exception No. 1. Read the full table in the published standard.

§ Table 130.7(C)(15)(a) — Arc flash PPE categories, AC

EquipmentCategoryArc flash boundary
Panelboards or other equipment ≤ 240 V119 in (485 mm)
Panelboards or other equipment > 240 V and ≤ 600 V23 ft (900 mm)
600 V class MCC — fault ≤ 65 kA, clearing ≤ 0.03 s25 ft (1.5 m)
600 V class MCC — fault ≤ 42 kA, clearing ≤ 0.33 s414 ft (4.3 m)
600 V class switchgear and switchboards420 ft (6 m)
Other 600 V class equipment25 ft (1.5 m)
NEMA E2 motor starters, 2.3 – 7.2 kV440 ft (12 m)
Metal-clad switchgear, 1 – 15 kV440 ft (12 m)
Metal-enclosed interrupter switchgear, 1 – 15 kV440 ft (12 m)
Other equipment 1 – 15 kV440 ft (12 m)
Arc-resistant equipment, doors closed and secured, within ratingN/AN/A
Two things to carry out of this table

The two MCC rows are the same equipment at two categories. The only difference is clearing time — and clearing time depends on maintenance.

For equipment ≤ 600 V protected by upstream current-limiting fuses or breakers rated 200 A or less, the category may be reduced by one — but never below Category 1.

§ Table 130.7(C)(15)(b) — Arc flash PPE categories, DC

Storage batteries, DC switchboards and other DC supply sources — excluding Article 320 capacitors — greater than 150 V and up to 600 V, based on a 2-second arc duration at a 455 mm (18 in) working distance.

Available fault currentCategoryArc flash boundary
Less than 1.5 kA23 ft (900 mm)
1.5 kA to less than 3 kA24 ft (1.2 m)
3 kA to less than 7 kA36 ft (1.8 m)
7 kA to less than 10 kA48 ft (2.5 m)

§ Table 130.7(C)(15)(c) — PPE by category

CategoryMinimum arc ratingKey clothing and equipment
14 cal/cm² (16.75 J/cm²)AR shirt and pants or coverall; face shield or hood; hard hat; safety glasses or goggles (SR); hearing protection (ear canal inserts); leather, AR or rubber insulating gloves (SR); leather footwear (AN)
28 cal/cm² (33.5 J/cm²)AR shirt and pants or coverall; hood, or face shield plus balaclava; hard hat; safety glasses or goggles (SR); hearing protection; gloves (SR); leather footwear
325 cal/cm² (104.7 J/cm²)Full AR layered system — shirt, pants, coverall, suit jacket and pants as required; arc flash suit hood; gloves (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear
440 cal/cm² (167.5 J/cm²)Full AR layered system; arc flash suit hood; gloves (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear

AN = as needed. AR = as required. SR = selection of one in the group required.

§ Table 130.5(G) — Incident energy analysis method

Incident energy at the working distanceRequired PPE
1.2 – 12 cal/cm²AR clothing with an arc rating ≥ the estimated incident energy; AR long-sleeve shirt and pants, coverall or arc flash suit (SR); AR face shield plus balaclava, or arc flash suit hood (SR); AR outerwear as needed; heavy-duty leather, AR or rubber insulating gloves with protectors (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear
Greater than 12 cal/cm²AR clothing with an arc rating ≥ the estimated incident energy; AR shirt and pants, coverall or arc flash suit (SR); arc flash suit hood — no face-shield option; AR outerwear as needed; AR gloves or rubber insulating gloves with protectors (SR); hard hat; safety glasses or goggles (SR); hearing protection; leather footwear
The practical difference between the bands

Above 12 cal/cm² a face shield and balaclava will not do — you need the hood. And plain heavy-duty leather gloves will not do — you need arc-rated gloves or rubber insulating gloves with protectors.

§ Tables 130.7(C)(7)(a) and (b) — Rubber insulating equipment

ClassMax AC use voltage (rms)Max DC use voltage (avg)Min. protector / glove cuff distance
00500 V750 V13 mm (0.5 in)
01,000 V1,500 V13 mm (0.5 in)
17,500 V11,250 V25 mm (1 in)
217,000 V25,500 V51 mm (2 in)
326,500 V39,750 V76 mm (3 in)
436,000 V54,000 V102 mm (4 in)
EquipmentWhen to test
GlovesBefore first issue; every 6 months thereafter
SleevesBefore first issue; every 12 months thereafter
BlanketsBefore first issue; every 12 months thereafter
CoversIf insulating value is suspect
Line hoseIf insulating value is suspect

New insulating equipment must have been tested within the previous 12 months before being placed in service. Issued equipment is retested per this table.